A website by Lamers Reinigingstechniek B.V., Zelhem, the Netherlands+31 (0)314 623 341 WhatsApp 06-38048347 info@lamersequipment.nlNL EN DE CS

Duct cleaning standards: EN 15780, VDI 6022 and NVRL

The most important duct cleaning standards are the European standard EN 15780:2025 for the cleanliness of ventilation systems, the German hygiene guideline VDI 6022 for air handling and the NVRL quality mark scheme for grease in kitchen extraction. In the Netherlands the legal basis does not lie in those standards, however, but in the Working Conditions Decree (Arbobesluit) and the Building Works Living Environment Decree (Bbl).

  • Family business with over 50 years in cleaning equipment
  • Danduct Clean DC4, PD4 and Intelligent Airnozzle
  • Duct brushes for ducts from 100 to 600 mm
  • Lamers Reinigingstechniek B.V. in Zelhem, the Netherlands
Duct cleaning standards: EN 15780, VDI 6022 and NVRL: portrait of René Hendriksen, Sales Account Manager at Lamers Reinigingstechniek (contact

René Hendriksen, Sales Account Manager
Call +31 (0)314 623 341, message us on WhatsApp 06-38048347 or request a callback.

Duct cleaning standards: EN 15780, VDI 6022 and NVRL: pD4 duct cleaner with power drill, flexible shaft and brushes at a ceiling valve (photo by

For a facility manager or facilities team the difference matters. The law says there must be enough clean air and that the installation must always be ready for use. The standards translate that into measurable cleanliness classes, inspection intervals and working methods. Insurers and clients can refer to them in their requirements.

Below you will find, for each standard, what it contains, what its status is and what you do with it in practice. Where figures come from trade publications rather than from the standard itself, we say so.

Duct cleaning standards: EN 15780, VDI 6022 and NVRL: grease layer in kitchen extract systems and dust load per cleanliness class (chart)
Grease layer in kitchen extract systems and dust load per cleanliness class. Source and reference date are shown below the chart.

Which standards and rules apply to clean air ducts?

The overview below puts the frameworks side by side. Pay attention to the status column: some of the well known documents have recently been replaced.

FrameworkWhat it coversStatus (reference date 6 October 2026)
EN 15780:2025Cleanliness of ventilation systems, assessment, cleaning method, frequencyPublished July 2025, replaces EN 15780:2011
VDI 6022 Part 1 (Blatt 1)Hygiene requirements for air handling installationsEdition January 2018
NVRL quality mark schemeCleanliness, mainly grease contamination in kitchen extraction and industryVersion of 24 June 2021, drawn up with TNO
Arbobesluit Art. 6.2Air renewal at the workplaceStatutory
Arbobesluit Art. 4.87bLegionella in air humidificationStatutory
Bbl Art. 3.67 ff. and 4.122 ff.Ventilation in existing buildings and new buildsStatutory; capacity for new builds via NEN 1087
NEN-EN 16798-3Performance requirements for ventilation of non-residential buildings2017 version withdrawn, successor from 2025
NADCA ACR 2025American standard for inspection, cleaning and verification2025 edition

In addition, the Dutch knowledge institute ISSO published a document in 2010 on quality requirements for ductwork systems in residential and non-residential buildings, and Eurovent gives practical requirements for inspection openings and cleaning methods in recommendation REC 6/7.

EN 15780:2025: what has changed compared with 2011?

EN 15780 is the European standard for the cleanliness of ventilation systems. The revised version appeared at the end of July 2025 via the Norwegian and British standards institutes; in Germany, DIN EN 15780:2026-07 was published with 49 pages, replacing the 2012 edition.

According to cleaning company Hamster Cleaning, the standard for the first time contains guidance on grease thickness in commercial kitchen extraction. That is a secondary source; the exact wording can be found in the standard itself, which you can buy from NEN or another standards institute.

EN 15780 duct cleanliness classes and dust limits from trade publications

The limit values for dust on the duct wall are widely quoted, but in the sources used on this site they come from trade publications and not from the text of the standard itself. Use them as guidance and check the standard before putting them in a contract.

Class or building typeDust on duct wallSource
Quality class lowLess than 4.5 g/m²Hamster Cleaning, on EN 15780
Quality class mediumLess than 3.0 g/m²Hamster Cleaning, on EN 15780
Quality class highLess than 0.6 g/m²Hamster Cleaning, on EN 15780
Offices, hotels, schools (medium risk)Less than 3.0 g/m², secondary duct up to 4.5 g/m²Trade article by Airmec
Finnish indoor climate class P1 / P21.0 / 2.5 g/m²CIB research, for comparison

The same trade article mentions a risk assessment every two years, and every year in high risk buildings such as hospitals and laboratories. How to turn that into a schedule is explained under air duct cleaning interval. For offices, the page on ventilation in commercial buildings works this out further.

VDI 6022 ventilation hygiene: inspections of air handling

VDI 6022 Part 1 is a German guideline with hygiene requirements for the design, construction and operation of air handling installations. Its aim is air that is harmless to health. It is not Dutch law, but you can include it as a hygiene framework in a maintenance contract.

In hospitals there is an additional obligation to have an air management plan for operating theatres. More on that under hospital ductwork cleaning.

NVRL quality mark and grease limits for kitchen extraction

The Dutch association of cleaning specialists for air handling systems (NVRL) drew up a quality mark scheme for the cleanliness of air handling systems together with TNO. The emphasis is on grease in the kitchen extraction of restaurants, hospitals, care homes and offices, and on industry.

ElementNVRL quality mark schemeEN 15780:2025 according to Hamster Cleaning
Action level500 µm of greaseLocally 500 µm or more: urgent cleaning
After cleaning / full cleanMaximum 200 µmOn average 200 µm or more: full cleaning
MeasurementWet film thickness gauge, accuracy 20 µmNot specified in the source
SamplesBehind every hood and per 10 m of ductNot specified in the source
Validity1 yearNot applicable

There is no statutory cleaning frequency for the hospitality sector, says KHN (Royal Dutch Hospitality Association), but fire insurers do require regular maintenance. Rabobank advises at least once a year, and twice for a restaurant with deep fryers. The practical side is covered under kitchen extract cleaning.

Legal requirements: the Arbobesluit and the Bbl

Where the standards provide measurable limits, the laws establish the duty. The key articles at a glance:

For schools, the Dutch Frisse Scholen (Fresh Schools) programme ties in with this; see fresh air in classrooms.

What do the standards say about the cleaning method itself?

Besides cleanliness limits, guidelines also set requirements for the way the work is done. Those requirements determine which equipment you need.

For rotary brushing in ducts of 100 to 600 mm up to 30 m deep, electric DC4 brushing machine for cleaning contractors is the purpose built tool; for narrow ducts with bends there is the air lance with camera. Sealing and negative pressure are handled with vent caps for duct cleaning and an extraction unit. The complete overview can be found under duct cleaning equipment for cleaning contractors.

From duct cleaning standards to a maintenance plan

A standard only becomes useful once you translate it to your own building. These five steps help:

  1. Decide for each installation which framework leads: EN 15780 for general ventilation, VDI 6022 for air handling with hygiene requirements, NVRL for kitchen extraction.
  2. Choose a cleanliness class that matches how the building is used.
  3. Record inspection intervals and who carries out the inspections.
  4. Describe the working method and the verification, as in cleaning ductwork professionally.
  5. Archive reports, photos and measured values for the insurer and the auditor.

Not sure which machine matches your requirements? Then contact Lamers from Lamers.

Air duct cleaning equipment from Lamers at a glance

Frequently asked questions: duct cleaning standards

Is EN 15780:2025 a legal requirement for duct cleaning in the Netherlands?

The sources on this page do not mention a legal obligation to follow EN 15780. The legal basis lies in the Working Conditions Decree (Arbobesluit), with sufficient uncontaminated air and installations that are always ready for use, and in the Bbl. EN 15780 makes those requirements measurable, and insurers or clients can refer to it in contracts.

What is the main difference between EN 15780:2011 and EN 15780:2025?

The 2025 version replaces the 2011 version and extends its application to the extract systems of commercial kitchens. It applies to new and existing systems over their entire service life. Informative Annex A contains tables with cleanliness classes, inspection intervals per class in months, acceptable cleanliness levels and requirements for new ducts.

Does EN 15780 also apply to industrial, medical and laboratory ventilation?

No. According to the description from the Norwegian standards institute, EN 15780:2025 applies to ventilation systems with the exception of industrial, medical and laboratory facilities. Industrial process installations are also excluded. For hospitals you therefore also look at the guidelines for air handling in operating theatres and at VDI 6022 as a hygiene framework.

Which dust limit belongs to cleanliness class high according to trade publications?

According to cleaning company Hamster Cleaning, which summarises EN 15780, the limit for quality class high is below 0.6 g/m² of dust on the duct wall. Medium is below 3.0 g/m² and low below 4.5 g/m². These figures come from a secondary source; check them against the text of the standard before including them in a contract.

How often does VDI 6022 call for a hygiene inspection of air handling?

According to TÜV Süd, every two years for installations with air humidification and every three years for installations without humidification. A first inspection is due before commissioning, after a major modification or if the installation has never been inspected. The repeat inspection includes, among other things, an assessment of the contamination in the ducts.

What does the NVRL quality mark scheme for kitchen extraction involve?

The scheme was drawn up by the NVRL together with TNO and focuses on grease contamination. At 500 µm of grease you have to take action, and after cleaning no more than 200 µm may remain. Measurements are taken with a wet film thickness gauge, behind every extract hood and per 10 metres of duct. The quality mark is valid for one year.

Which article of the Dutch Arbobesluit covers ventilation at the workplace?

That is Article 6.2 on air renewal. It requires sufficient uncontaminated air, installations that are always ready for use and a monitoring system that signals faults where health requires it. Article 6.4 is sometimes mentioned, but it concerns keeping out sunlight and therefore has nothing to do with ventilation.

At what grease layer thickness must an extract duct be cleaned according to the NVRL?

The NVRL quality mark scheme gives 500 µm as the action level. After cleaning, the grease layer may be no more than 200 µm. Hamster Cleaning describes comparable values for EN 15780:2025: on average 200 µm or more means full cleaning, locally 500 µm or more means urgent cleaning. A report with measurements before and after helps when dealing with the insurer.

Why do inspectors advise separating duct cleaning from the hygiene inspection?

Whoever does the cleaning is judging their own work. Eurofins therefore advises carrying out the VDI 6022 hygiene inspection separately from the cleaning, for an objective verdict. For a facilities team that cleans in house, this means having the final check or a sample inspection done by an external, independent inspector.

Which standard determines ventilation capacity for new builds under the Bbl?

For new builds, ventilation capacity under the Building Works Living Environment Decree is determined with NEN 1087, according to the Dutch government information point IPLO. The requirements themselves are in Article 4.122 onwards of the Bbl. For existing buildings, Articles 3.67 to 3.73 apply, which require a ventilation provision that prevents damage to health.

Sources and reference date

All facts on this page were checked on 6 October 2026.

Editorial team: Lamers Reinigingstechniek B.V., supplier of professional air duct cleaning equipment in Zelhem, the Netherlands. Updated on . See also the family business Lamers for cleaning contractors.

Request a quote or advice from Lamers

Duct cleaning standards: EN 15780, VDI 6022 and NVRL: portrait of René Hendriksen, Sales Account Manager at Lamers Reinigingstechniek (next to the

René Hendriksen, Sales Account Manager at Lamers, advises you on the machine, brushes and extraction for your jobs.

Briefly tell us what you clean (duct type, diameter, length, contamination and sector). Lamers will contact you with advice and a tailored quote.

Prefer direct contact? Call +31 (0)314 623 341, message us on WhatsApp 06-38048347 or email info@lamersequipment.nl.

Prefer a quick call first? Lamers will call you back

Duct cleaning standards: EN 15780, VDI 6022 and NVRL: rené Hendriksen, Sales Account Manager at Lamers, in an AI video in an office with an air
René Hendriksen, Sales Account Manager. AI video, 10 seconds.

Leave your number. René Hendriksen or a colleague from Lamers will call you back to discuss duct type, diameter and the right equipment.

Request a quote06-38048347